PPTmaster_BRC_050128.pot 25.03.2017 Rexroth Inline compact I/O technology in your control cabinet SERCOS III Components Abteilung; Vor- und Nachname
Rexroth Inline SERCOS III Block I/O Digital Inputs Connections for 16 digital sensors Connection of sensors in 2 and 3-wire technology Maximum permissible load current per sensor: 125 mA Combined Inputs and Outputs Connections for 16 digital sensors/actuators Each single channel can only be used as input or as output Connection of actuators in 2-wire technology Nominal current per output: 0.5 A Short-circuit and overload protected outputs Prototypes: Week 23/07 Electric Drives and Controls Stand 05/2006 PRM3 / Norbert Gehre
Rexroth Inline SERCOS III Block I/O Digital Electronic type plate: Component name Vendor code Device Name Device ID Revision Serial Number Operational hours Dimensions: 155.8 mm x 55 mm x 141 mm (width x height x depth) Ordering Data: MNR: R911170826 Type: R-ILB S3 24 DI16 DIO 16 SOS LP: 600 € Prototypes: Week 23/07 Electric Drives and Controls Stand 05/2006 PRM3 / Norbert Gehre
Rexroth Inline SERCOS III Block I/O Analog Inputs 4 differential analog signal inputs or 4 universal RTD inputs Connection of sensors in 2. 3. and 4-wire technology Sensor supply with channel-specific integrated short-circuit and overload protection Three current measuring ranges: 0 mA to 20 mA. ±20 mA. 4 mA to 20 mA Four voltage measuring ranges: 0V to 5V. ±5 V. 0 V to 10 V. ±10V Various RTD measuring ranges: E.g.. linear R: 0 Ω to 9500 Ω. Pt 100. Pt 1000. Ni 1000 16-bit measured value resolution (15 bits + sign bit) Adjustable filter times (4.5ms; 1.1ms) Prototypes: Week 29/07 Electric Drives and Controls Stand 05/2006 PRM3 / Norbert Gehre
Rexroth Inline SERCOS III Block I/O Analog Outputs: 2 universal analog signal outputs to connect either voltage or current signals Connection of actuators in 2-wire technology Three current ranges: 0 mA to 20 mA. ±20 mA. 4 mA to 20 mA Four voltage ranges: 0 V to 5 V. ±5 V. 0 V to 10 V. ±10 V Short-circuit-proof outputs Prototypes: Week 29/07 Electric Drives and Controls Stand 05/2006 PRM3 / Norbert Gehre
Rexroth Inline SERCOS III Block I/O Analog Electronic type plate: Component name Vendor code Device Name Device ID Revision Serial Number Operational hours Dimensions: 155.8 mm x 55 mm x 141 mm (width x height x depth) Ordering Data: MNR: R911170874 Type: R-ILB S3 24 AI4 AO2 SOS LP: 950 € Prototypes: Week 29/07 Electric Drives and Controls Stand 05/2006 PRM3 / Norbert Gehre
Rexroth Inline SERCOS III I/O SERCOS III Buscoupler Connects up to 62 standard Inline modules Automatic baudrate detection on localbus (500kBaud or 2MBaud) Inputs Connections for 8 digital sensors Connection of sensors in 2 and 3-wire technology Maximum permissible load current per sensor: 125 mA Outputs Connections for 4 digital actuators Connection of actuators in 2- and 3- wire technology Nominal current per output: 0.5 A Short-circuit and overload protected outputs Prototypes: Week 47/07 Electric Drives and Controls Stand 05/2006 PRM3 / Norbert Gehre
Rexroth Inline SERCOS III I/O SERCOS III Bus coupler Electronic type plate: Component name Vendor code Device Name Device ID Revision Serial Number Operational hours Dimensions: 80 mm x 70 mm x 121 mm (width x height x depth) Ordering Data: MNR: R911170875 Type: R-IL S3 PB BK DI8 DO4 SOS LP: approx.: 550 € *) *) not fixed! Prototypes: Week 47/07 Electric Drives and Controls Stand 05/2006 PRM3 / Norbert Gehre
Rexroth Inline SERCOS III Cabeling Free length: RKB0011 R911316888 Fix length: RKB0013 0.25 R911317797 0.35 R911317800 0.55 R911317801 Electric Drives and Controls Stand 05/2006 PRM3 / Norbert Gehre