Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Welcome Welcome to today’s presentation: Using HPL 2007/2008 Wiring.

Ähnliche Präsentationen


Präsentation zum Thema: "Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Welcome Welcome to today’s presentation: Using HPL 2007/2008 Wiring."—  Präsentation transkript:

1 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Welcome Welcome to today’s presentation: Using HPL 2007/2008 Wiring and connecting

2 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Torben Hinrichsen Thorsten Pschunder Industrial switchgear sales Moeller House Hamburg

3 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

4 IA-PP P.Merte Page - ‹Nr.›

5 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

6 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

7 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

8 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

9 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

10 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

11 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

12 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

13 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

14 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

15 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

16 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

17 IA-PP P.Merte Page - ‹Nr.›

18 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

19 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

20 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

21 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

22 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

23 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Exercises The customer wants to start an 11 kW delta 400 V with a star-delta circuit. This is to be implemented with a star-delta combination with overload relay. The changeover from star to delta is to take place after about 13 seconds. Question 1: How high is the rated motor current? Solution on last page of HPL: 21.7A

24 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Exercises The customer wants to start an 11 kW delta 400 V with a star-delta circuit. This is to be implemented with a star-delta combination with overload relay. The changeover from star to delta is to take place after about 13 seconds. Question 2: How do you go about finding the star-delta combination? Option 1: The way Table of contents, chapter, chapter contents Option 2: Index from page 18/26

25 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Motor: P=11 kW, AC-3 Rated operational voltage: 400 V Rated motor current: 21.7 A Contactor actuation: 230 V AC Solution: SDAINLM 22 (230V 50 Hz)

26 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Selected overload relay: ZB12-16

27 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

28 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Exercises The customer wants to install the star-delta combination SDAINLM 22 in an AP enclosure. Question 1: What enclosure goes with the SDAINLM 22 combination?

29 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

30 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

31 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Exercises Because of the cable length, the customer must lay a NYM 5×4 mm² cable for the star-delta combination. Question 1: Can the customer connect this cable to the mains contactor (DILM 15) (terminal capacity)? Option 1: Technical data in chapter Option 2: ????? (alphabetical index)

32 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008

33 Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Thank you for your time.


Herunterladen ppt "Observe protection mark to ISO 16016 Moeller House Hamburg /Hinrichsen-Pschunder / 2008 Welcome Welcome to today’s presentation: Using HPL 2007/2008 Wiring."